General Element Ranges and Accuracy
Phase Mho
Distance
Secondary Reach Setting Range:
0.05 - 64
Ω
at the line angle
Ground
Mho Distance
Secondary Reach Setting Range:
│
k
01
│
and
│
k
0
│
setting range*:
Angle k
01
and k
0
setting range*:
0.05 - 64
Ω
at the line angle
0 - 4
±180° in 0.1° steps
*
Note:
Same setting applies to Quadrilateral Ground Distance.
Quadrilateral
Distance
Secondary Reactive Reach:
Secondary Resistive Reach:
Nonhomogeneous Factor (T, degrees):
0.05 - 64
Ω
0.05 - 50
Ω
±20° in 0.1° steps
Out-of-Step
Distance
Secondary Reactance Setting Range:
Secondary Resistance Setting Range:
±96
Ω
±70
Ω
Load
Encroachment
Detection
Secondary Impedance Setting Range:
Forward Load Angle Setting (in degrees):
Reverse Load Angle Setting (in degrees):
0.05 - 64
Ω
-90° to +90°
+90° to 270°
Distance Element
Accuracy
Secondary Steady-State Error:
±5% of set reach ±0.01
Ω
at line angle (LA) for V > 5 V and I > 2 A
±10% of set reach ±0.01
Ω
at LA for 1 V < V < 5 V and 1 A < I < 2 A
Transient Overreach Error:
±5% of set reach, plus steady-state error
Negative-Sequence
Directional
Element
Secondary Positive-Sequence Current Restraint Range:
Secondary Forward Directional Current Supervision:
Secondary Reverse Directional Current Supervision:
Secondary Forward Directional Impedance Setting:
Secondary Reverse Directional Impedance Setting:
0.02 - 0.5
0.25 - 5 A
0.25 - 5 A
±64
Ω
±64
Ω
Supervisory
Overcurrent
Phase
Secondary Pickup Setting Range:
•
Supervises ground distance
0.5 - 100 A, ±0.05 A, ±3% of setting
Phase-to-Phase
Secondary Pickup Setting Range:
•
Supervises phase distance
1.0 - 170 A, ±0.05 A, ±3% of setting
Positive-Sequence
Secondary Pickup Setting Range:
•
Supervises OOS logic
1.0 - 100 A, ±0.05 A, ±3% of setting
Residual
Secondary Pickup Setting Range:
Transient Overreach:
•
Supervises ground distance
0.5 - 100 A, ±0.05 A, ±3% of setting
±5% of pickup
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......