7-22
Maintenance and Testing
Date Code 20011026
SEL-321/321-1 Instruction Manual
Consider the result of applying the following voltage and current signals to Equation 7.2:
ondary
sec
,
amps
90
2
I
ondary
sec
,
volts
180
10
V
90
ANG
1
Z
2
2
°
−
∠
=
°
∠
=
°
=
∠
2
*
2
]
)
90
-
2
•
90
(1
•
180
Re[10
=
c
2
Z
°
∠
°
∠
°
∠
4
ohms
20
-
=
c
2
Z
ohms
-5
=
c
2
Z
Coincidentally, these voltage and current signals could represent a forward single line-ground
fault on a system with a 90
°
impedance angle. Normally, a forward fault results in a negative
Z2c value.
Here is an example for a reverse single line-ground fault.
ondary
sec
,
amps
90
2
I
ondary
sec
,
volts
180
10
V
90
ANG
1
Z
2
2
°
∠
=
°
∠
=
°
=
∠
2
*
2
]
)
90
+
2
•
90
(1
•
180
Re[10
=
c
2
Z
°
∠
°
∠
°
∠
4
ohms
20
=
c
2
Z
ohms
5
=
c
2
Z
Notice that the result of Equation 7.2 is positive for a reverse fault and negative for a forward
fault. This result is consistent with actual behavior on the power system.
The relay determines fault direction by comparing the result of Equation 7.2 to forward and
reverse impedance thresholds that are dependent upon the Z2F and Z2R relay settings and the
magnitude of negative-sequence voltage divided by the magnitude of negative-sequence current.
When Z2c is less than the forward Z2 threshold, Z2FT, the fault is in the forward direction, so
the relay sets the 32QF element, if other supervisory conditions permit. When Z2c is greater
than the reverse Z2 threshold, Z2RT, the fault is in the reverse direction, so the relay sets the
32QR element, if other supervisory conditions permit.
The forward directional threshold is calculated using Equation 7.3 when Z2F is negative or
Equation 7.4 when Z2F is positive.
When Z2F
≤
0:
m
2
Z
•
0.25
-
F
2
Z
•
0.75
=
FT
2
Z
Equation
7.3
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......