Specifications
Date Code 20011026
SEL-321/321-1 Instruction Manual
Directional
Time-Overcurrent
Selectable Curve Shape:
Moderately inverse (US) or Longtime Standby (IEC)
Inverse (US) or Standard Inverse (IEC)
Very Inverse (US or IEC)
Extremely Inverse (US or IEC)
Phase Pickup setting range:
0.5 A - 16 A, ±0.05 A, ±3% of setting
Neg.-Seq. pickup setting range:
0.5 A - 16 A, ±0.05 A, ±3% of setting
Residual Pickup setting range:
0.5 A - 16 A, ±0.05 A, ±3% of setting
Time Dial setting range:
0.5 - 15 in 0.01 steps (US)
0.05 - 1 in 0.01 steps (IEC)
Timing: ±4% and ±1.5 cycles for current magnitudes between 2 and 20 multiples of
pickup.
Nondirectional
Residual/Neg.-Seq.
Overcurrent
Secondary Pickup setting range: 0.25 - 80 A, ±0.05 A, ±3% of setting
Transient Overreach: ±5% of pickup
Overvoltage
Pickup: 0 - 150 V, ±5% of setting, ±1 V
Transient Overreach: ±5% of pickup
Undervoltage
Pickup: 0 - 100 V, ±5% of setting, ±1 V
Transient Overreach: ±5% of pickup
Miscellaneous
Timers
Step Distance
Time Delay: 0 - 2000 cycles
Communications
Scheme
Time Delay: 0 - 2000 cycles
DCB Carrier Coordination
Time Delay: 0 - 60 cycles
Short
Delay
Time Delay: 0 - 2000 cycles
Long
Delay
Time Delay: 0 - 8000 cycles
Loss-of-Potential
Set
Time Delay: 1 - 60 cycles
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......