Date Code 20011026
Maintenance and Testing
7-47
SEL-321/321-1 Instruction Manual
(
)
(
)
(
)
(
)
(
)
*
T
1
I
I
0
k
1
ANG
1
Z
1
Im
*
T
1
I
V
Im
X
A
A
A
A
AG
°
∠
⋅
⋅
⋅
+
⋅
∠
°
∠
⋅
=
Equation
7.18
When T = 0°, as it does in the example relay settings, Equation 7.18 can be further
Simplified using the following identity:
( ) ( )
( )
(
)
(
)
(
)
0
k
1
I
ANG
1
Z
1
Im
*
I
V
Im
X
*
I
I
I
2
A
A
A
AG
A
A
2
A
+
⋅
⋅
∠
=
⋅
=
Equation
7.19
If we select a value for V
A
, it then becomes possible to use Equation 7.19 to calculate
the magnitude and angle of I
A
required to test the Zone 2 ground quadrilateral
distance element reactive reach.
For the example, select V
A
= 40.0
∠
0°. To simplify the reactance calculation, select
the angle of I
A
= -90° with respect to V
A
. For the Zone 2 element, XG2 = 9.36
Ω
,
∠
Z1ANG = 83.97°, and k0 = 0.726
∠
-3.69°.
(
)
(
)
(
)
°
−
∠
+
⋅
°
∠
⋅
°
∠
⋅
°
∠
=
69
.
3
726
.
0
1
97
.
83
1
Im
I
90
I
0
0
.
40
Im
36
.
9
2
A
A
The result of computing the imaginary portion of V
A
⋅
I
A
*
when I
A
lags V
A
by 90° is:
(
)
A
A
A
A
I
V
90
I
0
V
Im
⋅
=
°
∠
⋅°
∠
Substituting this into the equation above yields:
(
)
71
.
1
I
I
0
.
40
36
.
9
2
A
A
⋅
⋅
=
Solving for the magnitude of I
A
yields:
(
) (
)
amps
49
.
2
I
71
.
1
39
.
9
0
.
40
I
A
A
=
⋅
=
The Zone 2 ground distance element is forward-reaching in the example relay
settings. Thus, it is supervised by the forward directional element 32QF, as well as
the 50L2 and 50G2 phase and residual overcurrent elements. Applied phase current
must exceed the 50L2 setting, applied residual current must exceed the 50G2 setting,
and applied 3I2 must exceed the 50QF setting.
The 50L overcurrent elements operate based upon the magnitude of the phase
current. Using the current connections shown in Figure 7.6, the magnitude of I
A
is
equal to the magnitude of the applied test current.
With a 50L2 setting of 0.90 amps, 50L2 picks up when I
TEST
is greater than 0.90
amps.
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......