Date
(5 A N
OMINAL
R
ELAY
)
Date Code 20011026
(ZLIN, ZLOUT, M2P, N) (SEL-321-1 Relay)
Residual Time-Overcurrent Element Settings
Residual Time Overcurrent Element: Enable: (Y/N/S)
E51N
=
_________
Pickup: (0.5 - 16 amps sec., 3I
0
) 51NP
=
_________
Curve Family: (U1, U2, U3, U4, C1, C2, C3, C4)
51NC
=
_________
Time Dial: (US 0.5 - 15, IEC 0.05 - 1)
51NTD
=
_________
Reset Delay: (Y/N)
51NRS
=
_________
Torque Control: (32QF, 32QR, Z2G, N)
51NTC
=
_________
Residual Overcurrent Element Settings
Enable Number of Residual Instantaneous Overcurrent Levels: (N, 1, 2, 3, 4)
E50N
=
_________
Residual Inst. Overcurrent Pickup: Level 1: (0.25 - 80 amps sec., 3I
0
) 50N1
=
_________
Level 2: (0.25 - 80 amps sec., 3I
0
) 50N2
=
_________
Level 3: (0.25 - 80 amps sec., 3I
0
) 50N3
=
_________
Level 4: (0.25 - 80 amps sec., 3I
0
) 50N4
=
_________
Negative-Sequence Time Overcurrent Element Settings
Negative-Sequence Time Overcurrent: Enable: (Y/N/S)
E51Q
=
_________
Pickup: (0.5 - 16 amps sec., 3I
2
) 51QP
=
_________
Curve Family: (U1, U2, U3, U4, C1, C2, C3, C4)
51QC
=
_________
Time Dial: (US 0.5 - 15, IEC 0.05 - 1)
51QTD
=
_________
Reset Delay: (Y/N)
51QRS
=
_________
Torque Control: (32QF, 32QR, M2P, Z2G, N)
51QTC
=
_________
Negative-Sequence Overcurrent Element Settings
Enable Number of Neg.-Sequence Inst. Overcurrent Levels: (N, 1, 2, 3, 4)
E50Q
=
_________
Neg.-Seq. Inst. Overcurrent Pickup: Level 1: (0.25 - 80 amps sec., 3I
2
) 50Q1
=
_________
Level 2: (0.25 - 80 amps sec., 3I
2
) 50Q2
=
_________
Level 3: (0.25 - 80 amps sec., 3I
2
) 50Q3
=
_________
Level 4: (0.25 - 80 amps sec., 3I
2
) 50Q4
=
_________
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......