Date Code 20011026
Communications
3-3
SEL-321/321-1 Instruction Manual
Hardware Protocol
The following hardware protocol is designed for manual and automatic communications.
1. If RTS_CTS = N, RTS will always be asserted.
2. If RTS_CTS = Y, RTS deasserts when the relay is busy (momentarily unable to accept
characters).
3. Port 3 does not support RTS_CTS hardware handshaking.
4. If RTS_CTS = Y, the relay does not send characters until the CTS input is asserted.
Alarm Conditions
The SEL-321 Relay asserts the ALARM output until self-tests pass when power is applied and at
any diagnostic test failure. In addition to these, the ALARM output pulses with the commands
and conditions shown in Table 3.1.
Table 3.1: Commands With Alarm Conditions
Command Condition
2ACCESS
Entering Access Level 2 or
Three wrong password attempts
ACCESS
Three wrong password attempts
BREAKER
Entering Breaker Access Level or
Three wrong password attempts
COPY
Copying a group into the active setting group
GROUP
Changing the active setting group
PASSWORD
Any password is changed
SET commands
Changing the global settings, an active logic setting group, or the
active group setting
Main Board Jumpers
Installing and removing certain main board jumpers affects execution of some commands. Table
3.2 lists the jumpers you should be concerned with and their effects. See
Jumper Settings
in
Section 6: Installation
for details.
Table 3.2: Hardware Jumpers That Affect Commands
Jumper Comment
P7: J105
Disables password protection when installed
P7: J106
Enables OPEN and CLOSE commands when installed
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......