![Schweitzer Engineering Laboratories SEL-321 Instruction Manual Download Page 62](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-321/sel-321_instruction-manual_1216711062.webp)
2-38
Specifications
Date Code 20011026
SEL-321/321-1 Instruction Manual
Selecting Single-Pole or Three-Pole Tripping Logic
The relay uses single-pole tripping logic if:
•
Single-pole trip enable setting ESPT = Y, Y1, or
•
Programmable input variable SPTE is asserted.
Otherwise, the relay uses three-pole tripping logic.
Tripping Output Signals
There are four tripping output variables, which can be programmed to drive output contacts for
tripping breakers: TPA, TPB, TPC, and 3PT.
Variables TPA, TPB, and TPC are phase-dependent tripping signals, designed to control the
individual poles of a circuit breaker in single-pole tripping schemes.
Variable 3PT indicates three-pole trips.
Single-Pole Tripping Conditions
When the single-pole tripping logic is active, the SEL-321 Relay trips single-pole for the
following trip conditions:
•
Zone 1 SLG faults detected by the ground distance elements
•
Zone 2 SLG faults detected by the ground distance elements and permitted to trip through
the communications scheme logic.
•
DTA, DTB, DTC assigned and asserted.
•
See the special single-pole tripping appendix,
Appendix F
, for other schemes.
All other tripping conditions (including switch-onto-fault, time-step trips, overcurrent trips, and
trips during the SPO condition) cause three-pole trips.
Selecting Elements to Trip
The user selects the desired relay elements for unconditional trip, for switch-onto-fault, and for
tripping with communications assistance.
The user programs three variables with the desired elements, using the SET L command: MTU,
MTO, and MTCS.
MTU (Unconditional Trip Variable)
Include Zone 1 and time-delayed protective elements in this equation, for example:
MTU = M1P + Z1G + M2PT + Z2GT + M3PT + Z3GT + 51NT
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......