Communications
3-37
SEL-321/321-1 Instruction Manual
Button
Pushed
Results Displayed
Comment
→
1 DATE 12/01/92
DIST: 75.13
Displays third field of first event record, showing
distance to fault. $$$$$$ may be displayed under
some conditions to indicate indeterminate fault
location, or event is caused by TRIGGER
command.
→
1 DATE 12/01/92
GROUP 5
Displays fourth field of first event record,
showing setting group.
↑
2 DATE 12/01/92
TIME 2356:31.238
Displays Date/Time of second event record.
Pressing (
↓
) displays previous event record, (
↑
)
next event record.
EXIT
DEFAULT
DISPLAY
Defaults to display seen before TARGET button
was pushed unless an event occurred that would
normally update the display, in which case the
updated information will be displayed.
Meter Display
The METER display is updated every second. Two meter values are displayed at a time. Use the
(
↑
) and (
↓
) keys to move between meter pairs.
MET IA= -94.31
↑↓
IB= 76.05
Group Selector
When you select GROUP from Access Level 1, the active group and the group variable are
shown. To change Groups from the front panel, you first enter Access Level 2 or Breaker Access
Level using the OTHER command (see
). To change the group, use the up
arrow to increment the group variable, the down arrow to decrement it. When the desired group
variable is displayed, press SELECT/YES. The display shows:
Execute Group x
Are you sure?
If you choose SELECT/YES again, the keyboard group changes to the group selected. If the
group selection logic and inputs are in a state that uses the entered group as the active group, the
active group will be switched to the entered group. If you choose CANCEL/NO, the group
command is aborted and the default display is shown. (See also
Section 2: Specifications
for
discussion of group selection.)
Status Display
When you select STATUS, a STATUS report is displayed. The first row indicates if a warning or
failure state exists, or if all self-tests have passed. Use the (
↑
) and (
↓
) keys to scroll through the
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......