![Schweitzer Engineering Laboratories SEL-321 Instruction Manual Download Page 205](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-321/sel-321_instruction-manual_1216711205.webp)
Date Code 20011026
Applications
5-29
SEL-321/321-1 Instruction Manual
S
ETTINGS
S
HEET
Page
3
OF
10
FOR THE
SEL-321/321-1 R
ELAY
Date
(5 A
N
OMINAL
R
ELAY
)
Out-of-Step Blocking and Tripping Settings
Enable OOS: (Y/N)
EOOS
=
N
OOSB Enable:
Block Zone 1: (Y/N)
OOSB1
=
Block Zone 2: (Y/N)
OOSB2
=
Block Zone 3: (Y/N)
OOSB3
=
Block Zone 4: (Y/N)
OOSB4
=
Out-of-Step Block Time Delay (TDPU): (0.5 - 8000 cycles)
OSBD
=
Enable OOST: (I/O/N)
EOOST
=
Out-of-Step TOWI Time Delay (TDPU): (0.5 - 8000 cycles)
OSTD
=
Zone 5 Reactive Reach:
Top: (0 to ±96
Ω
sec.)
X1T5
=
Bottom: (0 to ±96
Ω
sec.)
X1B5
=
Zone 5 Resistive Reach:
Right: (0 to ±70
Ω
sec.)
R1R5
=
Left: (0 to ±70
Ω
sec.)
R1L5
=
Zone 6 Reactive Reach:
Top: (0 to ±96
Ω
sec.)
X1T6
=
Bottom: (0 to ±96
Ω
sec.)
X1B6
=
Zone 6 Resistive Reach:
Right: (0 to ±70
Ω
sec.)
R1R6
=
Left: (0 to ±70
Ω
sec.)
R1L6
=
Zone 6 Positive-Sequence Overcurrent Supervision: (1 - 100 amps sec., I1) 50ABC
=
Load-Encroachment Settings
Enable Load-Encroachment: (Y/N)
ELE
=
Y
Load Impedance: Forward: (0.05 - 64
Ω
sec.)
ZLF
=
9.22
Reverse: (0.05 - 64
Ω
sec.)
ZLR
=
9.22
Load Angle:
Positive Forward: (-90° to +90°)
PLAF
=
30
Negative Forward: (-90° to +90°)
NLAF
=
-30
Positive Reverse: (+90° to +270°)
PLAR
=
150
Negative Reverse: (+90° to +270°)
NLAR
=
210
Negative-Sequence Directional Element Settings
Forward Directional Z2 Threshold: (±64
Ω
sec.)
Z2F
=
0.77
Forward Directional Current Threshold: (0.25 - 5 amps sec., 3I2)
50QF
=
0.50
Reverse Directional Z2 Threshold: (±64
Ω
sec.)
Z2R
=
5.45
Reverse Directional Current Threshold: (0.25 - 5 amps sec., 3I2)
50QR
=
0.50
Positive-Sequence Current Restraint Factor: (0.02 - 0.5 unitless)
a2
=
0.07
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......