3-30
Communications
Date Code 20011026
SEL-321/321-1 Instruction Manual
Category Setting
Comment
TIMEOUT
0
Time relay waits after last command received before relay
reverts to Access Level 0 and aborts any command in
process (0.00-30.0 minutes). If set to 0, port never
times out.
AUTO
Y
Y = Port set to AUTO.
RTS_CTS
N
N = RS232 request to send - clear to send handshake
protocol is OFF (see
earlier
in this section).
Y = Protocol on. Should be set to Y for use with modem.
MBT = MBT9600 modem used with PROTOCOL = MB.
FAST_OP
(SEL-321-1 Relay
only)
N
N = Disable fast operate command processing.
Y = Enable fast operate command processing. (See Fast
Operate Command Processing Application Guide).
STATUS
STATUS allows inspection of self-test status. The relay automatically executes the STATUS
command whenever the self-test software enters a warning or failure state. If this occurs, the
relay transmits a STATUS report from the port(s) designated automatic (see SET command,
AUTO setting). Type STATUS 4 to view the status information four times.
The STATUS report format appears below:
=>STATUS <ENTER>
STATUS <ENTER>
STATUS <ENTER>
STATUS <ENTER>
EXAMPLE: BUS B, BREAKER 3 Date: 02/01/93 Time: 15:16:42.580
SELF TESTS
W=Warn F=Fail
IA IB IC VA VB VC MOF
OS 0 0 0 0 0 0 0
+5V_PS +5V_REG -5V_REG +12V_REG -115V_PS -15V_PS
PS 4.96 5.10 -4.98 11.93 -12.09 15.02 -15.21
TEMP RAM ROM A/D CR_RAM EEPROM SETTINGS
26.1 OK OK OK OK OK OK
Relay Enabled
=>
Table 3.13 describes the STATUS report. For a description of self-test and test parameters, see
Self-Test
in
Section 2: Specifications
.
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......