2
Command Summary
Date Code 20011026
SEL-321 Instruction Manual
Access Level B
CLOSE
Asserts the CLOSE condition.
GROUP
Specifies currently selected group. Use GROUP n to change selected group to n.
OPEN
Asserts trip condition.
Access Level 2
COPY m n
Copies settings and logic from setting Group m to Group n.
PASSWORD
Shows or sets passwords. Command pulses ALARM contacts closed momentarily
after password entry. PAS 1 OTTER sets Level 1 password to OTTER. PAS 2 TAIL
sets Level 2 password to TAIL.
SET n
Use to enter group settings. If n argument omitted, edits active group.
SET G
Use to enter new global settings.
SET L
Use SET L n to edit Group n's logic settings. Selects active logic group to edit.
SET P
Use SET P n to edit Port n's settings. Changes active port's settings.
TARGET
Shows target values, and defines target group for display. TAR n displays target row
n. TAR R command resets front panel targets to TAR 1.