4-2
Event Reporting
Date Code 20011026
SEL-321/321-1 Instruction Manual
Table 4.3: Event Record Type
Type Comment
TRIP
EXT
EXTC
ER
Report triggered by TPA, TPB, TPC, or 3PT assertion, no fault.
Report triggered by assertion of EXT (external trigger) designated
input.
Report triggered by TRIGGER command.
Report triggered by MER SEL
OGIC
®
control equations, but no fault
detecting element asserted at trigger instant.
The MER mask triggers event reports on the rising-edge of the first element in the mask. The
relay does not generate multiple event reports when additional relay elements within MER pick
up; only the first relay element of any continuous sequence triggers an event report.
Tripping and External Trigger events are rising-edge sensitive. For these events, event reports
are generated independent of the state of MER. The relay triggers a second report for the same
event if
TPA, TPB, TPC,
or
3PT
asserts. Thus, the relay records the beginning and end of each
event. A second event report is not provided, however, if
TPA
,
TPB
,
TPC,
or
3PT
first assert at
or less than seven cycles after the first report is triggered.
Event report triggering and time stamping is referenced to the 16th quarter-cycle of data with
1/8-cycle resolution.
S
UMMARY
E
VENT
R
EPORT
The summary report is automatically transmitted to port(s) designated AUTO regardless of
access level. The summary event report includes:
•
Line terminal identifier (set in the relay setting procedure)
•
Date and time
•
Event type (see Table 4.4) and fault location
•
System frequency at the time of the trip (this is 1/16th of the sampling frequency at the
time of the trip)
•
Front panel relay targets asserted at the last row of the event report
•
The magnitude and angle of positive-sequence polarizing voltage memory at the time of
trigger
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......