8 .3
Para. #
Function
Default
Range
Description
P01
Pair Device
RLAY_CTL
RLAY_CTRL
AKL Relay controllers: Displays controller ID & Zone number
RDTR_VLV
ARV/AVA Valve Actuators: Displays total # of paired valves
RCV1
AX10RF Receiver (RX1): Cn = Connected
RCV2
AX10RF Receiver (RX2): Cn = Connected
P02
Internal Schedule
N (inactive)
N (inactive)
Settings S 03 through S 10 are not available
Y (active)
Schedule Mode
P03
Temperature
Control
Method
AUTO
AUTO
RLAY CTL (HEAT), RCV1, RCV2 = TPI
RLAY CTRL (COOL) = DLTA 1 .0°F (0 .5°C)
RDTR VLV = DLTA 0 .5°F (0 .25°C)
TPI
TPI control is based on the current temperature differential
(Proportional) and historical performance (Integral) to determine the
next duty cycle percentage .
DLTA 1 .0/0 .5
Heat turns on when T
room
= T
setpoint
– Delta, Cooling turns on when
T
room
= T
setpoint
+ Delta
DLTA 0 .5/0 .25
P04
Minimum
OFF Time
180 seconds
180 - 300 seconds
Minimum period that the thermostat must be off before starting a new
cycle to prevent short cycling . (TPI Only)
P08
Temperature
Offset
0 .0°F or °C
±6 .0°F (3 .0°C)
Temperature offset for current active temperature sensor
P09
Freeze
Protection
41°F (5°C)
41 to 63°F
(5 to 17°C)
Minimum allowable temperature for the system . Below the
specified temperature a heat demand will be signaled .
Off
P10
Maximum Target
Temperature
95°F (35°C)
42 to 95°F
(5 .5 to 35°C)
Maximum allowable temperature setting for heating and cooling mode .
P11
Minimum Target
Temperature
41°F (5°C)
41 to 94°F
(5 to 34 .5°C)
Minimum allowable temperature setting for heating and cooling mode .
P15
External Sensor
OFF (Disabled)
ON (Enable)
OFF (Disable)
Enable or Disable external sensor for remote sensing . “EXTERNAL” is
only displayed if P16 function is set to “AIR” .
P16
External Sensor
Function
FLR (Floor)
FLR (Floor)
or AIR
Floor temperature is used to control the room temperature based on
the room and radiant floor temperature .
Air is used when a remote sensor is used in place of the internal
thermostat sensor .
P17
Maximum Floor
Temperature
81°F (27°C)
52 to 95°F
(11 to 35°C)
Maximum temperature that a heat demand will be signaled . P15
must be ON and External Sensor Function must be FLR . Not
displayed for RDTR VLV .
P18
Minimum Floor
Temperature
50°F (10°C)
41 to 95°F
(5 to 35°C)
Minimum temperature that a cooling demand will be signaled .
P15 must be ON and External Sensor Function must be FLR . Not
displayed for RDTR VLV .
The table below titled AWRT10RF Wireless Radiant Thermostat Parameters lists parameters
available from the thermostat screen & keypad .
AWRT10RF Thermostat Settings & Parameters