72
Reference Manual
00809-0100-4530, Rev DD
May 2016
4.7.3
Non-intrinsically safe output
With non-intrinsically safe power supply in non-hazardous installations or
explosion-proof/flameproof installations, wire the transmitter as shown in
.
Note
Make sure the power supply is off when connecting the transmitter.
Figure 4-5. Wiring Diagram for Non-Intrinsically Safe Installations (HART)
For HART communication a minimum load resistance of 250
within the loop is required.
For maximum load resistance. See
(Explosion/Flameproof) and
(Non-hazardous installations).
For explosion-proof/flameproof applications the resistance between the negative terminal
on the transmitter and the power supply must not exceed 435
.
Note
For explosion-proof/flameproof installations, make sure the transmitter is grounded to the
internal ground terminal inside the terminal compartment in accordance with national and
local electrical codes.
Load resistance
Power
supply
Field
Communicator
Rosemount 5300 Series
Radar Transmitter
HART modem
RRM
AMS
™
Suite
250