110
Reference Manual
00809-0100-4530, Rev DD
May 2016
Rosemount Radar Master (RRM) includes tools to estimate the dielectric constant of the
current product:
The Dielectric Constant Chart lists the dielectric constant of a large number of
products. The Dielectric Constant Chart can be opened with one of the following
methods:
- Select
View
>
Dielectric Constant Chart
menu option.
- In the
Configuration Wizard - Environment
window, click the
Dielectric Chart button
.
- Select
Setup
>
Tank
, click the
Environment
tab, and then click the
Dielectric
Constant Chart
button
.
The Upper Product Dielectric Constant Calculator
lets you calculate the
dielectric constant of the upper product based on the following input:
- actual upper product thickness,
- the dielectric constant value stored in the transmitter, and
- the upper product thickness presented by the transmitter.
The Upper Product Dielectric Constant Calculator is available via the dielectric
calculator button
in the
Configuration Wizard - Environment
window or the
Tank/Environment
window.
Volume
9.
Select
Volume Calculation Method
.
HART command: [2, 1, 5].
F
OUNDATION
Fieldbus parameters:
Calculation method:
TRANSDUCER 1300 > VOL_VOLUME_CALC_METHOD
Tank diameter:
TRANSDUCER 1300 > VOL_IDEAL_DIAMETER