![Rosemount 5300 Series Reference Manual Download Page 336](http://html1.mh-extra.com/html/rosemount/5300-series/5300-series_reference-manual_1487396336.webp)
May 2016
Reference Manual
00809-0100-4530, Rev DD
322
1.
Verify the basic configuration for device has been performed.
2.
Make sure the correct probe type is selected.
a.
RRM
: Select
Setup
>
Tank
.
DD:
Select
Configure/Setup
>
Tank
.
b. Click the
Probe
tab.
c. In the
Probe type
list, select
Coaxial HTHP
for probe type 3V and
Rigid Single
HTHP 0.3
″
(8mm)
for probe type 4U.
d.
RRM
: Click
Store
.
DD
: Click
Send
.
3.
Check that Mounting Type is set to Pipe/Chamber and select inner diameter.
a.
RRM
: Select
Setup
>
Tank
.
DD:
Select
Configure/Setup
>
Tank
.
b. Click the
Geometry
tab.
c. In the
Mounting Type
list, select
Pipe/Chamber
.
d.
DD
: Click
Send
.
e. In the
Inner Diameter, Pipe/Chamber/Nozzle list
, select the corresponding inner
diameter.
f.
RRM
: Click
Store
.
DD
: Click
Send
.
4.
RRM: Select
Setup
>
Advanced
.
DD
: Select
Configure/Setup
>
Advanced
.
5.
Click the
Vapor Compensation
tab.
6.
Make sure the correct reflector type is selected.
a. In the
Reference Reflector Type
list, select reference reflector according to table
below.
b.
RRM
: Click
Store
.
DD
: Click
Send
.
7.
RRM
: Select the
Use Vapor Compensation
checkbox. Then click
Store
.
DD
: Select the
Use Vapor Compensation
checkbox. Then click
Send
.
8.
Click the
Calibrate Vapor Compensation
button, and follow the on-screen
instructions.
Probe
type
Reference reflector type
Length RRM parameter
DD parameter
3V
Short
Coax, l=350 mm
Coax l=350mm (RR B3 in old DD versions)
Long
Coax, l=500 mm
Coax l=500mm (RR B4 in old DD versions)
4U
Short
d=13 mm, l=350 mm
d=13 mm, l=350 mm
(RR A6 in old DD versions)
Long
d=13 mm, l=500 mm
d=13 mm, l=500 mm
(RR B2 in old DD versions)