Rosemount 5300 Series with HART® to Modbus® Converter
May 2016
Reference Manual
00809-0100-4530, Rev DD
409
Rosemount 5300 Series with HART® to Modbus® Converter
3.
Select
Enable Modbus Communication
and click
OK
.
4.
If the HMC is configured for Modbus ASCII or Levelmaster communication cycle the
power to the transmitter (the HMC will then communicate using Modbus RTU for
20 seconds and under that time it is possible to connect with RRM).
5.
Open the
Search Device
window and make sure Modbus is selected in the Protocol
list.
6.
Search for HMCs by selecting
Scan Address Range
, and choose a start and end
address for Modbus. The default HMC Modbus address is 246.
7.
Click the
Start Scan
button.
8.
Click
OK
to connect when the device is found.
9.
From the
Service
menu, choose the
Enter Service Mode
option.