Rosemount 5300 Series with HART® to Modbus® Converter
May 2016
Reference Manual
00809-0100-4530, Rev DD
406
Rosemount 5300 Series with HART® to Modbus® Converter
J.11.6
ScadaPack
Figure J-14. Wiring Diagram for Connecting Rosemount 5300 Modbus to
SCADAPack 32
Table J-24. Parameter Values (In Case of SCADAPack 32)
The Input Register Base Number needs to be added to the Input Register address of the
Rosemount 5300 Series Transmitter. In this case, register 1302 needs to have 31303
entered as the address etc.
J.11.7
Kimray Inc. DACC 2000/3000
This table shows input types in Kimray Inc. IMI software and the corresponding value. The
communication port must be configured to use “Tank Levels” protocol.
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
Floating Point
Input Register Base Number
30001
RS-485 on COM1
1 +5 V
2 RX-
3 TX-
4 GND
5 RX+
6 TX+
7 Not Used
8 Not Used
SCADAPack32
MA
MB
POWER +
POWER -
5300 Modbus
Power Supply
+ 8 to + 30 Vdc
(max. rating)
REF