7.16
Write protecting a transmitter
A Rosemount 5300 Series Transmitter can be protected from unintentional configuration
changes by a password protected function. The default password is 12345. It is
recommended that this password is not changed to facilitate service and maintenance of
the transmitter.
RRM:
Tools
>
Lock/Unlock Configuration Area
.
AMS Suite:
Tools
>
Service
>
Lock/Unlock Device
.
HART Command: [3, 2, 1, 2].
DeltaV:
1.
In the DeltaV Explorer, select the transmitter icon, and right click the Transducer
1100 block icon.
2.
Select the
Unlock/Lock Device
option.
7.17
Enter service mode in RRM
In RRM, service functions for advanced users are available for the Rosemount 5300 Series
Transmitter. Setting RRM into Service Mode, all the Service menu options in RRM are
enabled. The default password for enabling the Service Mode is “admin”. The password can
be changed by selecting the
Change Password
option from the
Service
menu.
7.18
Viewing input and holding registers
Measured data is continuously stored in the
Input Registers
. Viewing the contents of the
Input Registers, advanced users can check that the transmitter works properly.
The
Holding Registers
store various transmitter parameters, such as configuration data,
used to control the measurement performance.
Unlock/Lock
TRANSDUCER1100