May 2016
Reference Manual
00809-0100-4530, Rev DD
356
MIN_CYCLE_T
21
Time duration of the shortest cycle interval of which the resource is capable.
MISC_OPTION
47
Indicates which miscellaneous licensing options are enabled.
MODE_BLK
05
The actual, target, permitted, and normal modes of the block:
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take on
Normal: Most common mode for actual
NV_CYCLE_T
23
Minimum time interval specified by the manufacturer for writing copies of NV
parameters to non-volatile memory. Zero means it will never be automatically
copied. At the end of NV_CYCLE_T, only those parameters which have changed
need to be updated in NVRAM.
OUTPUT_BOARD_SN
53
Output board serial number.
PWA_SIMULATE
85
Parameter allowing simulation of PWA alarms.
RB_SFTWR_REV_ALL
51
The string will contains the following fields:
Major rev: 1-3 characters, decimal number 0-255
Minor rev: 1-3 characters, decimal number 0-255
Build rev: 1-5 characters, decimal number 0-255
Time of build: 8 characters, xx:xx:xx, military time
Day of week of build: 3 characters, Sun, Mon,...
Month of build: 3 characters, Jan, Feb.
Day of month of build: 1-2 characters, decimal number 1-31
Year of build: 4 characters, decimal
Builder: 7 characters, login name of builder
RB_SFTWR_REV_BUILD
50
Build of software that the resource block was created with.
RB_SFTWR_REV_MAJOR
48
Major revision of software that the resource block was created with.
RB_SFTWR_REV_MINOR
49
Minor revision of software that the resource block was created with.
RECOMMENDED_ACTION 68
Enumerated list of recommended actions displayed with a device alert.
RESTART
16
Allows a manual restart to be initiated. Several degrees of restart are possible.
They are the following:
1 Run – nominal state when not restarting
2 Restart resource – not used
3 Restart with defaults – set parameters to default values. See
START_WITH_DEFAULTS below for which parameters are set.
4 Restart processor – does a warm start of CPU.
RS_STATE
07
State of the function block application state machine.
SAVE_CONFIG_BLOCKS
62
Number of EEPROM blocks that have been modified since last burn. This value
will count down to zero when the configuration is saved.
SAVE_CONFIG_NOW
61
Allows the user to optionally save all non-volatile information immediately.
SECURITY_IO
65
Status of security switch.
SELF_TEST
59
Instructs resource block to perform self-test. Tests are device specific.
SET_FSTATE
29
Allows the FAIL_SAFE condition to be manually initiated by selecting Set.
SHED_RCAS
26
Time duration at which to give up on computer writes to function block RCas
locations. Shed from RCas shall never happen when SHED_ROUT = 0
SHED_ROUT
27
Time duration at which to give up on computer writes to function block ROut
locations. Shed from ROut shall never happen when SHED_ROUT = 0
SIMULATE_IO
64
Status of simulate switch.
Parameter
Index number Description