May 2016
Reference Manual
00809-0100-4530, Rev DD
366
I.1
Simulation
To support testing, you can either change the mode of the block to manual and adjust the
output value, or you can enable simulation through the configuration tool and manually
enter a value for the measurement value and its status. In both cases, you must first set the
ENABLE jumper on the field device.
Note
All fieldbus instruments have a simulation jumper. As a safety measure, the jumper has to be
reset every time there is a power interruption. This measure is to prevent devices that went
through simulation in the staging process from being installed with simulation enabled.
With simulation enabled, the actual measurement value has no impact on the OUT value or
the status.
Figure I-2. Analog Input Function Block Schematic
Analog Measurement
Access
Analog
Meas.
CHANNEL
SIMULATE
OUT_SCALE
XD_SCALE
FIELD_VAL
L_TYPE
IO_OPTS
PV_FTIME
MODE
STATUS_OPTS
HI_HI_LIM
HI_LIM
LO_LO_LIM
LO_LIM
ALARM_HYS
ALARM_TYPE
OUT_D
OUT
PV
Convert
Cutoff
Filter
Status
Calc.
Alarm
Detection
Note
OUT = block output value and status.
OUT_D = discrete output that signals a selected alarm condition.
LOW_CUT