Installation/Wiring
1-3
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
Mounting Clearances
Operating Temperatures
Refer to the Drive, Fuse and Circuit Breaker Ratings tables in
for information on drive ambient operating temperatures.
AC Supply Source
Considerations
PowerFlex drives are suitable for use on a circuit capable of delivering up to
a maximum of 200,000 rms symmetrical amperes, 600 volts with
recommended fuses/circuit breakers. Refer to the PowerFlex 700S Drive
with Phase II Control Reference Manual, publication PFLEX-RM003…,
for actual interrupt ratings based on circuit breaker or fuse choice.
If a Residual Current Detector (RCD) is used as a system ground fault
monitor, only Type B (adjustable) devices should be used to avoid nuisance
tripping.
101.6mm
(4.0 in.)
101.6mm
(4.0 in.)
50.
8
mm (2.0 in.)
50.
8
mm (2.0 in.)
No Adhesive Label
(see below)
101.6mm
(4.0 in.)
101.6mm
(4.0 in.)
With Adhesive Label
(see below)
!
ATTENTION: To guard against personal injury and/or
equipment damage caused by improper fusing or circuit breaker
selection, use only the recommended line fuses/circuit breakers
specified in
.