Installation/Wiring
1-11
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
Figure 1.2 Frames 5 & 6 Jumper and Transformer Locations (Frame 5 shown)
Frame 6 Transformer Tap Access
The transformer is located behind the Power Terminal Block in the area
shown in
. Gain access by releasing the terminal block from the
rail. To release terminal block and change tap:
1. Locate the small metal tab at the bottom of the end block.
2. Press the tab in and pull the top of the block out. Repeat for next block if
desired.
3. Select appropriate transformer tap.
4. Replace block(s) in reverse order.
WIRE RANGE: 14-1/0 AWG (2.5-
3
5 MM
2
)
TORQUE:
3
2 IN-LB (
3
.6 N-M)
S
TRIP LENGTH: 0.67 IN (17 MM)
U
S
E 75 C CU WIRE ONLY
POWER TERMINAL RATING
S
WIRE RANGE: 6-1/0 AWG (16-
3
5 MM
2
)
TORQUE: 44 IN-LB (5 N-M)
S
TRIP LENGTH: 0.
83
IN (21 MM)
GROUND TERMINAL RATING
S
(PE)
3
00 VDC EXT PWR
S
PLY TERM (P
S
+, P
S
-)
WIRE RANGE: 22-10 AWG (0.5-4 MM
2
)
TORQUE: 5.
3
IN-LB (0.6 N-M)
S
TRIP LENGTH: 0.
3
5 IN (9 MM)
17
21
INPUT AC
OUTPUT
Option
a
l
Comm
u
nic
a
tion
s
Mod
u
le
9
Phase Selection
Jumper
Fan Voltage
LINE
TYPE
S
PARE 1
S
PARE 2
3
-PH 1-PH
4
8
0 Volt T
a
p
600 Volt T
a
p
690 Volt T
a
p
400 Volt T
a
p