Programming and Parameters
3-59
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
390 SL
MultErr
Cnfg
Enter a value to configure the Drive Module's response to a SynchLink Multiplier error. Refer
to
[SL Mult State] for possible causes for multiplier errors.
•
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
•
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when
this event occurs.
•
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault
bit, in response to this event.
•
3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault
bit, in response to this event.
•
4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate
fault bit, in response to this event.
Default
Options:
2 =
0 =
1 =
2 =
3 =
4 =
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
391
DPI CommLoss Cfg
Enter a value to configure the drive's response to the failure of a DPI port.
•
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
•
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when
this event occurs.
•
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault
bit, in response to this event.
•
3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault
bit, in response to this event.
•
4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate
fault bit, in response to this event.
Default
Options:
2 =
0 =
1 =
2 =
3 =
4 =
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
392
NetLoss DPI Cnfg
Enter a value to configure the drive's response to a communication fault from a network card
at a DPI port.
•
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
•
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when
this event occurs.
•
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault
bit, in response to this event.
•
3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault
bit, in response to this event.
•
4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate
fault bit, in response to this event.
Default
Options:
2 =
0 =
1 =
2 =
3 =
4 =
“FltCoastStop”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
393 BusUndervoltCnfg
Enter a value to configure the drive's response to the DC Bus voltage falling below the
minimum value.
•
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
•
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when
this event occurs.
•
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault
bit, in response to this event.
•
3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault
bit, in response to this event.
•
4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate
fault bit, in response to this event.
Default
Options:
1 =
0 =
1 =
2 =
3 =
4 =
“Alarm”
“Ignore”
“Alarm”
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp”
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
!
ATTENTION: Risk of injury or equipment damage exists.
[SL MultErr Cnfg] lets you determine the
action of the drive if communications are disrupted. By default this parameter causes the drive fault and coast
to a stop. You can set this parameter so that the drive continues to run. Precautions should be taken to ensure
that the setting of this parameter does not create hazards of injury or equipment damage.
!
ATTENTION: Risk of injury or equipment damage exists.
[DPI CommLoss Cfg] lets you determine
the action of the drive if communications are disrupted. By default this parameter causes the drive fault and
coast to a stop. You can set this parameter so that the drive continues to run. Precautions should be taken to
ensure that the setting of this parameter does not create hazards of injury or equipment damage.
!
ATTENTION: Risk of injury or equipment damage exists.
[NetLoss DPI Cnfg] lets you determine
the action of the drive if communications are disrupted. By default this parameter causes the drive fault and
coast to a stop. You can set this parameter so that the drive continues to run. Precautions should be taken to
ensure that the setting of this parameter does not create hazards of injury or equipment damage.