3-62
Programming and Parameters
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
412
Power EE TP Sel
Enter or write a value to select drive power EEPROM data displayed in
[Power EE TP Data]. The default is 0 “Zero”.
Note: Options 74 - 92 were changed and options 93 - 111 were added for firmware version 3.01.
413
Power EE TP Data
Default:
Min/Max:
0
-/+2200000000
RO Real
414 Brake/Bus
Cnfg
Configures the brake and bus operation of the drive.
•
Set bit 0 “Brake Enable” to enable the operation of the internal brake transistor.
•
Set bit 1 “Brake Extern” to configure the brake to use an external resistor.
•
Set bit 2 “Bus Ref High” to select the "high" voltage setting as the turn-on point for the Bus Voltage Regulator. With the "high" setting brake operation starts
when bus voltage reaches the value of
[BusReg/Brake Ref], and Bus Voltage Regulator operation starts when bus voltage reaches the value of Par
415 [BusReg/Brake Ref] plus 4.5%. With the "low" setting, the bus regulator turns on first at the value set by Par 415 [BusReg/Brake Ref] and then the
dynamic braking turns on when there are any transients above the value set in Par 415 [BusReg/Brake Ref].
•
Set bit 3 “Bus Reg En” to enable the Bus Voltage Regulator. The output of the Bus Voltage Regulator is summed with
[Regen Power Lim] and fed into
the Power Limit Calculator. It, in effect, reduces regenerative torque references when the bus voltage is too high.
Notes: This parameter was changed to non-linkable and bits 5 and 6 were added for future use - not active for use with firmware version 3.01. Remove bits 5 and
6 for firmware version 4.001 - not used.
415 BusReg/Brake
Ref
Sets the “turn-on” voltage for the bus regulator and brakes. Enter a percentage of the high
voltage setting for the voltage class. For example, on a 400-480V drive,
Note: The minimum value for frame 5 and up, 600V AC input drives was changed from
110.5000 to 100.0000 for firmware version 4.002.
(1) The minimum value is 100.0000 for frame 5 and up, 600V AC input drives.
Units:
Default:
Min/Max:
%
111.0000
110.5000
(1)
/117.8000
RW Real
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
Options:
0 = Zero
19 = Bus VltScale
38 = IGBT Rated A
61 = Convt Type
80 = HH1 P/B ID
99 = HH2 P/B ID
1 = Volt Class
20 = Sml PS Watts
39 = IGBT V Thres
62 = DC Bus Induc
81 = HH1 S/W ID
100 = HH2 S/W ID
2 = Assy Rev
21 = Sml PS Min V
40 = IGBT Slope R
63 = AC Inp Induc
82 = HH1 P/B Rev
101 = HH2 P/B Rev
3 = ASA S/N
22 = Lrg PS Watts
41 = IGBT Sw Engy
64 = Precharg Res
83 = HH1 S/W Rev
102 = HH2 S/W Rev
4 = Manuf Year
23 = Lrg PS Min V
44 = IGBT CS Tres
65 = PrechThrm Tc
84 = HH1 Extr Data
103 = HH2 ExtrData
5 = Manuf Month
24 = Inv Rated Kw
45 = IGBT CS Tc
66 = Mtr NP Units
85 = HH1 VoltIndx
104 = HH2 VoltIndx
6 = Manuf Day
25 = Inv Rated V
46 = Diode V Thrs
67 = Mtr NP Power
86 = HH1 SizeIndx
105 = HH2 SizeIndx
7 = Tst ProcStat
26 = Inv Rated A
47 = Diode SlopeR
68 = Mtr NP Volts
87 = HH1 Option
106 = HH2 Option
8 = Life PwrCycl
27 = Inv 1min Amp
48 = Diode JC Tr
69 = Mtr NP Amps
88 = HH1 HrdPrdct
107 = HH2 HrdPrdct
9 = Life Pwrup
28 = inv 3sec Amp
49 = Diode JC Tc
70 = Mtr NP Freq
89 = HH1 H/W Mdfy
108 = HH2 H/W Mdfy
10 = Life RunTime
29 = SW OverC Amp
50 = GBT Tjmax
71 = Mtr NP RPM
90 = HH1 1V/Amp
109 = HH2 1V/Amp
11 = Kw Accum
30 = DC Bus Cap
51 = HS Max DegC
72 = Mtr IR Vdrop
91 = HH1 2s/Amp
110 = HH2 2s/Amp
12 = Mw Hrs Accum 31 = Min PWM Khz
52 = DB IGBT Amp
73 = Mtr Id Ref
92 = HH1 Scale
111 = HH2 Scale
13 = Inv High Vlt
32 = Max PWM Khz
53 = DB ohms
74 = HH1 Data Rev
93 = HH2 Data Rev
14 = Reserved
33 = Dfl PWM Khz
54 = DB E Jo/degC
75 = HH1 Dev Type
94 = HH2 Dev Type
15 = Fan/Pwr Cntl
34 = PWM Dead us
55 = DB EB C/Watt
76 = HH1 Serial #
95 = HH2 Serial #
16 = Temp Sensor
35 = Drive Frame
56 = DB B Jo/degC
77 = HH1 Test Date
96 = HH2 TestDate
17 = Phs AmpScale
36 = IGBTs per Pk
57 = DB BA C/Watt
78 = HH1 Vcn Code
97 = HH2 Vcn Code
18 = Gnd AmpScale 37 = GBT Rated V
60 = DB Ambt Tmax
79 = HH1 CrsCncID
98 = HH2 CrsCncID
Options
Res
er
ve
d
Res
er
ve
d
Res
er
ve
d
Res
er
ve
d
Res
er
ve
d
Res
er
ve
d
Res
er
ve
d
Res
er
ve
d
Res
er
ve
d
Res
er
ve
d
Res
er
ve
d
Res
er
ve
d
Bus
Re
g
En
Bus
Re
f High
Br
ak
e Ex
ter
n
Br
ak
e Ena
ble
Default
0
0
1
1
0
0
0
0
0
0
0
0
1
1
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = False
1 = True
111
2
×
480
VDC
=
×