K-2
SynchLink™ Board for PowerFlex® 700S Drives with Phase II Control
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
Table K.A SynchLink Cables and Accessories
Important: Do not overtighten tie-wraps.
Table K.B Fiber Optic Cable Assembly Specification
Description Cat.
No.
2 x 25 cm Fiber Optic Link
1403-CF 000
2 x 1 M Fiber Optic Link
1403-CF 001
2 x 3 M Fiber Optic Link
1403-CF 003
2 x 5 M Fiber Optic Link
1403-CF 005
10 M Fiber Optic Link
1403-CF 010
20 M Fiber Optic Link
1403-CF 020
50 M Fiber Optic Link
1403-CF 050
100 M Fiber Optic Link
1403-CF 100
250 M Fiber Optic Link
1403-CF 250
500 M Fiber Optic Bulk
1403-CF BLK
Termination Kit
1403-NTOL
Connector (10)
1403-N10
Splice Bushing (5)
1403-N11
Pulling Bullet
1403-N12
Fiber Stripper Tool
1403-N13
SynchLink Fiber-Hub, 1 input, Base
1751-SLBA
SynchLink Fiber-Hub, 4 output, “Star” Splitter
1751-SL4SP
SynchLink Bypass Switch
1751-SLBP/A
Parameter
Value
Connecting Cables
200/230 micron HCS (Hard Clad Silica)
Versalink V-System
Lucent Technologies,
Specialty Fibers Technology Division
Maximum
Cable Length
300 meters with no more than one splice or one adapter
Minimum
Cable Length
1 meter
Minimum inside bend radius 25.4mm (1 in.) Any bends with a shorter inside radius can permanently
damage the fiber optic cable. Signal attentuation increases with
decreased inside bend radii.
Operating Wavelength
650 nm (Red)
Data Rate
5 Mbps
Maximum
Node Count
10 - Daisy Chain,
256 - Star Configuration