Supplemental Information
A-23
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
Table A.AA 600 Volt AC Input Frames 9 - 14 Drive Protection Devices
20DE125
6
125
–
117
121.6 150
250
150
375
375
250
–
–
–
–
–
100
93
96.6
125
200
125
375
375
150
–
–
–
–
20DE144
6
150
–
135
140.5 175
300
175
400
400
250
–
–
–
–
–
125
117
121.6 150
275
150
375
375
250
–
–
–
–
(1)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are
maximum.
(3)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip
settings must be set to US NEC code. Not to exceed 1300% FLA.
(6)
Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7)
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on
480V or 600V Delta/Delta systems.
(8)
The AIC ratings of the Bulletin 140M Motor Protector may vary. See publication 140M-SG001.
Drive
Catalog
Number
Fr
am
e
HP Rating Input Ratings
Dual Element
Time Delay
Fuse
Non-Time
Delay Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(5)
140M Motor Starter with Adjustable Current Range
(6)(7)
ND
HD
Amps
kVA
Min.
(1)
Max.
(2)
Min.
(3)
Max.
(4)
Max.
(4)
Max.
(6)
Available Catalog Numbers
(8)
Drive
Catalog
Number
Fra
m
e
HP Rating
Input
Ratings
Dual Element Time Delay
Fuse
Non-Time Delay Fuse
Bussmann Style
Semi-Conductor Fuse
Circuit
Breaker
(5)
Motor Circuit
Protector
(7)
ND
HD
Amps
Min.
(2)
Max.
(4)
Min.
(2)
Max.
(4)
Max
(6)
Max.
(6)
20DE170
9
150
–
164
225
375
225
500
170M3819
500
250
–
150
139
175
300
175
500
170M3819
500
200
20DE208
9
200
–
201
275
450
275
600
170M3819
600
300
–
150
164
225
375
225
500
170M3819
500
250
20DE261
10
250
–
252
325
575
325
775
170M5813
700
350
–
200
201
275
450
275
600
170M5813
600
300
20DE325
10
350
–
314
400
725
400
950
170M5813
900
450
–
250
252
325
575
325
775
170M5813
750
400
20DE385
10
400
–
372
475
850
475
1100
170M5813
1100
500
–
350
314
400
725
400
950
170M5813
900
450
20DE416
10
450
–
402
525
900
525
1200
170M5813
1200
550
–
350
314
400
725
400
950
170M5813
900
450
20DE460
11
500
–
444
575
(1 per phs)
300
(2 per phs)
1000
575
(1 per phs)
300
(2 per phs)
1300
170M8547
1300
600
–
400
372
475
(1 per phs)
250
(2 per phs)
850
475
(1 per phs)
250
(2 per phs)
1100
170M8547
1100
500
20DE502
11
500
–
485
625
(1 per phs)
325
(2 per phs)
1100
625
(1 per phs)
325
(2 per phs)
1500
170M8547
1500
650
–
500
444
575
(1 per phs)
300
(2 per phs)
1000
575
(1 per phs)
300
(2 per phs)
1300
170M8547
1300
600
20DE590
11
600
–
570
725
(1 per phs)
375
(2 per phs)
1300
725
(1 per phs)
375
(2 per phs)
1700
170M5813
1700
800
–
500
485
625
(1 per phs)
325
(2 per phs)
1100
625
(1 per phs)
325
(2 per phs)
1500
170M5813
1500
700
20DE650
12
700
–
628
800
(1 per phs)
400
(2 per phs)
1400
800
(1 per phs)
400
(2 per phs)
1900
170M5813
1900
900
–
650
570
725
(1 per phs)
375
(2 per phs)
1300
725
(1 per phs)
375
(2 per phs)
1700
170M5813
1700
800
20DE750
12
800
–
724
950
(1 per phs)
475
(2 per phs)
1600
950
(1 per phs)
475
(2 per phs)
2200
170M5813
2200
1000
–
700
628
800
(1 per phs)
400
(2 per phs)
1400
800
(1 per phs)
400
(2 per phs)
1900
170M5813
1900
900
20DE820
(1)
12
900
–
792
1000
(1 per phs)
500
(2 per phs)
1800
1000
(1 per phs)
500
(2 per phs)
2400
170M5813
2400
1100
–
700
628
800
(1 per phs)
400
(2 per phs)
1400
800
(1 per phs)
400
(2 per phs)
1900
170M5813
1900
900
20DE920
13
1000
–
888
1200
(1 per phs)
600
(2 per phs)
(3)
2000
(3)
1200
(1 per phs)
600
(2 per phs)
(3)
2700
(3)
170M6466
(3)
2700
1200
–
900
792
1000
(1 per phs)
500
(2 per phs)
(3)
1800
(3)
1000
(1 per phs)
500
(2 per phs)
(3)
2400
(3)
170M6466
(3)
2400
1100