Programming and Parameters
3-37
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
242 Encoder1
PPR
Sets the pulse per revolution rating of the feedback device connected to the Encoder 1 input.
This parameter must be set to one of the values displayed in bold in Table 242A below.
Units:
Default:
Min/Max:
PPR
1024
10/20000
RW 16-bit
Integer
245
Spd Fdbk TP Sel
Enter or write a value to select the data displayed in
[Spd Fdbk TP RPM] and
[Spd Fdbk TP Data].
Note: Option values 5 - 15 were changed to “Reserved” and option 41 “First Diff” was added
for firmware version 2.04.
Default:
Options:
0 =
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =
14 =
15 =
16 =
17 =
18 =
19 =
20 =
“Zero”
“Zero”
21 = “E0 EPR”
“Clock Time”
22 = “E0 Edge Mode”
“InactvFbkDev”
23 = “E0 nMax”
“ActiveFbkDev”
24 = “E0 Error”
“MCP Fdbk Dev”
25 = “E0 Qloss pk”
“Reserved”
26 = “E0 Ploss pk”
“Reserved”
27 = “E0 PlevlHist”
“Reserved”
28 = “E1 Edge Time”
“Reserved”
29 = “E1 dEdge”
“Reserved”
30 = “E1 dTime”
“Reserved”
31 = “E1 EPR”
“Reserved”
32 = “E1 Edge Mode”
“Reserved”
33 = “E1 nMax”
“Reserved”
34 = “E1 Error”
“Reserved”
35 = “E1 Qloss pk”
“Reserved”
36 = “E1 Ploss pk”
“MCP PPR”
37 = “E1 PlevlHist”
“MCP 2^n”
38 = “E0 Delta2Err”
“E0 Edge Time”
39 = “E1 Delta2Err”
“E0 dEdge”
40 = “EOB Present”
“E0 dTime”
41 = “First Diff”
246
Spd Fdbk TP RPM
Displays the value selected in
[Spd Fdbk TP Sel] in RPM. This display should only be
used if the selected value is floating point data.
Units:
Default:
Min/Max:
Scale:
RPM
0.0
-/+8.0 pu
[Motor NP RPM] = 1.0pu
RO Real
247
Spd Fdbk TP Data
Displays the value selected in
[Spd Fdbk TP Sel]. This display should only be used if
the selected value is integer data.
Default:
Min/Max:
0
-/+32768
RO 16-bit
Integer
249
Fdbk Option ID
Displays information about the Feedback Option.
•
Bits 15-11 indicate Module ID Number.
•
Bits 10-6 indicate Version Number.
•
Bits 5-3 indicate Revision Number High.
•
Bits 2-0 indicate Revision Number Low.
Hexadecimal 1000 indicates resolver, hexadecimal 2000 indicates old high-resolution board,
and hexadecimal 2040 indicates new high-resolution board.
Options:
250
FB Opt0 Posit
Displays the position feedback (accumulator) from the feedback option card port 0.
Default:
Min/Max:
0
-/+2147483648
RO 32-bit
Integer
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
Table 242A: PPR Rating Values
n =
2
n
=
x
mod 75
mod 125 mod 225 mod 375 mod 625 mod1125
0
1
75
125
225
375
625
1125
1
2
150
250
450
750
1250
2250
2
4
300
500
900
1500
2500
4500
3
8
600
1000
1800
3000
5000
9000
4
16
1200
2000
3600
6000
10000
18000
5
32
2400
4000
7200
12000
20000
--
6
64
--
--
--
--
--
--
7
128
--
--
--
--
--
--
8
256
--
--
--
--
--
--
9
512
--
--
--
--
--
--
10
1024
--
--
--
--
--
--
11
2048
--
--
--
--
--
--
12
4096
--
--
--
--
--
--
13
8192
--
--
--
--
--
--
14
16384
--
--
--
--
--
--
N N NNN
N N NNN
N NNN
Module ID No.
Version No.
Revision No. Low
N NNN
Revision No. High