Programming and Parameters
3-101
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
854
Dig Out2 OffTime
Defines the amount of time between a True to False transition on the output status and the
corresponding change in state of Digital Output 2. If a transition on an output condition occurs
and starts the time delay and the output condition returns to its original state before the delay
timer reaches the setpoint, the delay timer will be aborted and the corresponding output status
or digital output will not change state.
Note: This parameter was added for firmware version 3.01.
Units:
Default:
Min/Max:
Sec
0.0
0.0/600.00
RW 16-bit
Integer
855
Rly Out3 Sel
Identifies the signal used on Digital Output 3. If the desired signal is not available in the
selection list, choose option 0 - “User Select” and link with
[Rly Out3 Bit] to select the desired parameter for output.
Default:
Options:
1 =
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 =
14 =
“Not Fault”
“User Select”
15 = “Torque Limit”
“Not Fault”
16 = “Power Limit”
“Not Alarm”
17 = “Fault”
“Ready”
18 = “Alarm”
“Running”
19 = “Command Dir”
“Reserved”
20 = “Actual Dir”
“Reserved”
21 = “Jogging”
“Enable On”
22 = “In Position”
“Active”
23 = “Posit Watch1”
“At Speed”
24 = “Posit Watch2”
“At Setpt 1”
25 = “Cmpr 1 A</=B”
“Above Setpt 2”
26 = “Cmpr 1 A>/=B”
“At ZeroSpeed”
27 = “Cmpr 2 A</=B”
“Speed Limit”
28 = “Cmpr 2 A>/=B”
“CurrentLimit”
856
Rly Out3 Data
Link a word to this parameter that will control the Relay Output 3. The bit within the selected
word that will control Relay Output 3 is set by
[Rly Out3 Bit].
Default:
Min:
Max:
00000000000000000000000000000000
00000000000000000000000000000000
11111111111111111111111111111111
✓
RW 32-bit
Boolean
857
Rly Out3 Bit
Selects the bit, from the word linked to
[Rly Out3 Data] that will change the status of
the Relay Output 3 (e.g., when Par 857 [Rly Out3 Bit] equals 0, bit 0 of Par 856 [Rly Out3
Data] will control the Relay Output 3).
Default:
Min/Max:
0
-32/31
✓
RW 16-bit
Integer
858
Rly Out3 On Time
Defines the amount of time between a False to True transition on the output status and the
corresponding change in state of Relay Output 3. If a transition on an output condition occurs
and starts the time delay and the output condition returns to its original state before the delay
timer reaches the setpoint, the delay timer will be aborted and the corresponding output status
or relay output will not change state. Par 858 [Rly Out3 On Time] can be disabled by setting
the delay time to 0 (zero).
Note: This parameter was added for firmware version 3.01.
Units:
Default:
Min/Max:
Sec
0.00
0.00/600.00
RW 16-bit
Integer
859
Rly Out3 OffTime
Defines the amount of time between a True to False transition on the output status and the
corresponding change in state of Relay Output 3. If a transition on an output condition occurs
and starts the time delay and the output condition returns to its original state before the delay
timer reaches the setpoint, the delay timer will be aborted and the corresponding output status
or relay output will not change state.
Note: This parameter was added for firmware version 3.01.
Units:
Default:
Min/Max:
Sec
0.00
0.00/600.00
RW 16-bit
Integer
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype