PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
Appendix
A
Supplemental Information
Chapter Objectives
Specifications
For Information on …
See Page...
DPI Communication Configurations
Drive Fuse & Circuit Breaker Ratings
List of Motors with Compatible Thermistor Ratings
Drive Frame Size to HP/kW Ratings Cross Reference
Category
Specification
Frames 1-6 (690V Drive frames 5 & 6 only)
Frames 9 & up
Protection
Drive
200-208V 240V
380/400V 480V
600V
(frames
0-4)
600V /
690V
(frames
5&6)
380/400V
480V
500V 600V
690V
AC Input Overvoltage Trip: 300VAC
300VAC
600VAC
600VAC
863VAC
863VAC
675VAC
675V AC
675V AC
889VAC
889VAC
Bus Overvoltage Trip:
405VDC 405VDC 810VDC 810VDC 1164VDC 1164VDC 911VDC
911VDC
911VDC
1200VDC
1200VDC
Bus Undervoltage Trip:
Adjustable
Adjustable
Nominal Bus Voltage:
281VDC 324VDC 540VDC 648VDC 810VDC 931VDC 540VDC
648VDC
645VDC
810VDC
931VDC
All Drives
Heat Sink Thermistor:
Monitored by microprocessor overtemp trip
Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Software Current Limit:
Hardware Current Limit:
Instantaneous Current
Limit:
Calculated value, 105% of motor rated to 200% of drive rated
105% of 3 sec. rating (158%-210%)
143% of 3 sec rating (215%-287%)
Calculated value, 105% of motor rated to 200% of drive rated
360% of rated Heavy Duty current (typical)
—
Line Transients:
Up to 6000 volts peak per IEEE C62.41-1991
up to 6000 volts peak per IEEE C62.41-1991
Control Logic Noise
Immunity:
Showering arc transients up to 1500V peak
Showering arc transients up to 1500V peak
Power Ride-Thru:
15 milliseconds at full load
15 milliseconds at full load
Logic Control Ride-Thru
0.25 sec., drive not running
0.25 seconds, drive not running
Ground Fault Trip:
Phase-to-ground on drive output
Phase-to-ground on drive output
Short Circuit Trip:
Phase-to-phase on drive output
Phase-to-phase on drive output