2. SPECIFICATIONS
IMS01J02-E4
15
Digital output
Number of outputs:
8
points
Output type:
Open collector output
Number of common points:
Vcc: 2 points, GND: 2 points (8 points/common)
Isolation method:
Photocoupler
isolation
Load voltage:
12 to 24 V DC
Maximum load current:
0.1 A/point, 0.8 A/common
Output data
:
Digital output can be selected from the following:
Temperature alarm (Alarm 1, Alarm 2)
Heater break alarm (HBA)
Burnout
TI Alarm (Alarm 1, Alarm 2)
AI Alarm (Alarm 1, Alarm 2)
Control loop break alarm (LBA)
Temperature rise completion
Temperature rise completion
FAIL output
PLC communication status
Unused