7. MODBUS
IMS01J02-E4
128
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Alarm interlock release
[H-TIO-
, H-CIO-A,
H-TI-
, H-AI-
]
WO U
1: Release (1 only)
Cascade ON/OFF
[H-CIO-A]
R/W C
0: OFF 1: ON
Setting will be valid in master channel.
0
Cascade gain
[H-CIO-A]
R/W C
9.999 to
10.000
As the cascade gain is valid only in the slave
channel, the polling or selecting of the same
value is made also in the master channel.
1.000
Cascade bias
[H-CIO-A]
R/W C
99.99 to
100.00 %
As the cascade bias is valid only in the slave
channel, the polling or selecting of the same
value is made also in the master channel.
50.00
Positioning output
neutral zone
[H-TIO-K]
R/W C
0.1 to 10.0 % of motor time
2.0
Motor time
[H-TIO-K]
R/W C
5 to 1000 seconds
10
Integrated output limiter
[H-TIO-K]
R/W C
100.0 to 200.0 % of motor time
150.0
Manual positioning
output value
[H-TIO-K]
R/W C
5.0 to
105.0 %
0.0
Setting change rate
limiter
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W C
0.0 to 100.0 % of span/minute
0.0
Output limiter high
[For Heat/Cool control:
Heat-side output limiter
(high)]
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W C
[Heat control, Position proportioning control
and Speed control]
Output limiter low to 105.0 %
[Heat/Cool control]
Heat-side output limiter (high):
5.0 % to
105.0 %
Heat-side output limiter (low):
5.0 % (fixed)
100.0 *
Item stored in the memory area.
* Heat control (H-TIO-
/H-CIO-A): 100.0
Heat/Cool control (H-TIO-
/H-CIO-A): 100.0
Position proportioning control (H-TIO-K): 100.0
Speed control (H-SIO-A): 100