7. MODBUS
IMS01J02-E4
127
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Temperature rise
completion trigger
[H-TIO-
, H-CIO-A]
R/W C 0: Unused 1: Used
1
Do not set “1: Used” in H-TIO-H/J module
and H-SIO-A module, because temperature
rise completion is not judged.
0
CT channel setting
[H-CT-A]
R/W C 0 to 20 (0: Unused)
Allocates the channels for H-TIO-
module
to the input channels of H-CT-A module.
The factory
set value
varies
depending
on the
specifications
when
ordering.
Control RUN/STOP
transfer
[H-PCP-J]
R/W U 0: Control STOP 1: Control RUN
0
Memory area number
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W U 1 to 8
1
Temperature rise
completion soak time
[H-TIO-
, H-CIO-A]
R/W U 0 to 360 minutes
0
Module initialization
2
[H-PCP-J]
R/W U 0: Normal state (Initialization is not
executed)
1: Initialize only the new module
(Only modules which are not recognized
by the H-PCP-J module are initialized)
2: Initialize all modules
Returns to 0 after the module is initialized.
0
1
If the channel of each of the H-TIO-H/J and H-SIO-A modules is set “1: Used,” it does no reach the
completion of temperature rise. As a result, the state of this completion (control unit) which is judged
by performing the
OR
operation of all the channels cannot be attained, thereby continuing the
incompletion of temperature rise.
2
Initialize method for changing the module composition
To change module configuration, use the following procedures:
When a module is added to the control unit ................................... Initialize only the new module
When a module is deleted from the control unit ............................ Initialize only the new module
When the module is replaced with a different model ..................... Initialize only the new module
When a module is inserted (added) between the modules
in the control unit ........................................................................... Initialize all modules
To change the arrangement of the modules in the control unit ...... Initialize all modules
When “Initialize all modules” is performed, the set values of the setting data of all
modules (in the unit) will change (be initialized).
Before performing “Initialize all modules”, be sure to make a record of the set values
(normal setting data and initial setting data) of all modules. After performing
“Initialize all modules”, be sure to check the set values (normal setting data and initial
setting data) of all modules.
Continued on the next page.