6. RKC COMMUNICATION
IMS01J02-E4
74
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
H-CT-A module heater
break alarm status
[H-CT-A]
AH
1 RO C
0: Normal
1: Break
2: Welding
Comprehensive alarm
status
[H-PCP-J]
AJ
6 RO U
0 to 2047 *
Alarm status is expressed as a
bit image in decimal number.
Positioning monitor
[H-TIO-K]
M8
6 RO C
5.0 to
105.0 %
Positioning output
neutral zone
[H-TIO-K]
V3
6
R/W
C
0.1 to 10.0 % of motor time
2.0
Motor time
[H-TIO-K]
TJ
6
R/W
C
5 to 1000 seconds
10
Integrated output limiter
[H-TIO-K]
OS
6
R/W
C
100.0 to 200.0 % of motor
time
150.0
Manual positioning
output value
[H-TIO-K]
OO
6 R/W
C
5.0 to
105.0 %
0.0
* Each alarm status is assigned as a bit image in binary numbers. However, send data from the SR Mini
HG SYSTEM be changed to decimal ASCII code from the bit image in binary numbers.
Bit 15 ·························· Bit 0
Bit image:
0000000000000000
Bit data 0: OFF 1: ON
Continued on the next page.
Bit 0: Logical
OR
of alarm 1 status in all channels
Bit 1: Logical
OR
of alarm 2 status in all channels
Bit 2: Logical
OR
of burnout alarm status in all
channels
Bit 3: Logical
OR
of heater break alarm status in all
channels
Bit 4: Temperature rise completion status
Bit 5: Logical
OR
of AI alarm 1 status in all channels
Bit 6: Logical
OR
of AI alarm 2 status in all channels
Bit 7: Logical
OR
of control loop break alarm status in
all channels
Bit 8: Logical
OR
of TI alarm 1 status in all channels
Bit 9: Logical
OR
of TI alarm 2 status in all channels
Bit 10: Logical
OR
of TI burnout alarm status in all
channels
Bit 11 to Bit 15 are unused.