7. MODBUS
IMS01J02-E4
132
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
AT bias
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W C Within
input span range
0 *
ON/OFF control
differential gap (upper)
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W
C
0.00 to 10.00
of span
0.02
ON/OFF control
differential gap (lower)
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W
C
0.00 to 10.00
of span
0.02
Manipulated output
value at input error
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W
C
5.0 to
105.0 %
(Heat control, Position proportioning control,
Speed control)
105.0 to
105.0 %
(Heat/Cool control)
0.0
Direct/Reverse action
selection
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W C 0: Direct action
1: Reverse action
If the Direct/Reverse action selection is
changed, all of the settings corresponding to
the channels in the relevant module return to
the default values.
Setting will be invalid in Heat/Cool control.
The factory
set value
varies
depending
on the
specifications
when
ordering.
Hot/Cold start selection
[H-TIO-
, H-CIO-A,
H-SIO-A]
R/W C 0: Hot start
At restarting
Operation mode
→
Same as mode before the power failure
Output value
→
Same as value before the power failure
1: Cold start
At restarting
Operation mode
→
Same as mode before the power failure
Output value
→
Output limiter low
1
* The position of the decimal point differs depending on the input range.
Continued on the next page.