6. RKC COMMUNICATION
IMS01J02-E4
81
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
Hot/Cold start selection
[H-TIO-
, H-CIO-A,
H-SIO-A]
XN
1 R/W
C 0: Hot start
At restarting
Operation mode
→
Same as mode before
the power failure
Output value
→
Same as value before
the power failure
1: Cold start
At restarting
Operation mode
→
Same as mode before
the power failure
Output value
→
Output limiter low
1
Start determination
point *
[H-TIO-
, H-CIO-A]
SX
6 R/W
C 0.0 to 100.0
of span
(Deviation setting from the
temperature set value)
Setting will be invalid in
H-SIO-A module.
3.0
* On restarting after power failure, if the temperature measured value (PV) is within the setting range
by the start determination points, the hot start will definitely be carried out. If the temperature
measured value (PV) is outside this range, the operation will begin with the start condition with was
selected by the Hot/Cold start selection (Identifier: XN).
Continued on the next page.
Plus side start
determination point
Minus side start
determination point
The start condition with
was selected by the
Hot/Cold start selection
The start condition with
was selected by the
Hot/Cold start selection
Forced hot start
Temperature set value
(SV)
Start determination
range