6. RKC COMMUNICATION
IMS01J02-EE4
78
Data of identifier H3 with H-TIO-
/H-CIO-A module is different from H-SIO-A module.
Data is discriminated by channel number (module number).
Identifier H3: For H-CIO-A module ....... Cascade DI function selection
For H-SIO-A module ..... DI process selection
For the channel number, see the
8.2.9 Assignment of channels (P. 179)
.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
Input range number
[H-TIO-
, H-CIO-A,
H-SIO-A]
XI
6 R/W
C H-TIO-A/B/C/D/K/P: 0 to 63
H-TIO-E/F/G/R, H-CIO-A:
0 to 120
H-TIO-H/J, H-CIO-A: 0 to 12
H-SIO-A: 0 (Fixed)
If the input range number is
changed, all of the settings
corresponding to the channels
in the relevant module return to
the default values.
See
Input range table (P. 103)
The factory
set value
varies
depending
on the
specifications
when
ordering.
Setting limiter high
[H-TIO-
, H-CIO-A,
H-SIO-A]
SH
6 R/W
C TC/RTD input:
Setting limiter low to
Input range (high)
Input range
(high)
Voltage/Current input,
H-SIO-A:
Setting limiter low to
Display scale high
Display
scale high
Setting limiter low
[H-TIO-
, H-CIO-A,
H-SIO-A]
SL
6 R/W
C TC/RTD input:
Input range (low) to
Setting limiter high
Input range
(low)
Voltage/Current input,
H-SIO-A:
Display scale low to
Setting limiter high
Display
scale low
Digital filter
[H-TIO-
, H-CIO-A,
H-SIO-A]
F1
6 R/W
C H-TIO-A/B/C/D/K/P
0 to 100 seconds (0: OFF)
H-TIO-E/F/G/H/J/R,
H-CIO-A, H-SIO-A
0.0 to 100.0 seconds
(0.0:
OFF)
0 or 0.0
Input error
determination point
(high)
[H-TIO-
, H-CIO-A,
H-SIO-A]
AV
6 R/W
C TC/RTD input:
Within input range
Input range
(high)
Voltage/Current input,
H-SIO-A:
Within display scale range
Display
scale high
Continued on the next page.