5. SETTINGS BEFORE OPERATION
IMS01J02-E4
46
COM.PORT3 setting switch (SW3)
SW3
Data bit configuration
1 2
OFF OFF Data 8-bit, Without parity, Stop 1-bit
ON OFF Data 7-bit, Odd parity, Stop 1-bit
OFF ON Data 7-bit, Even parity, Stop 1-bit
ON ON Data 7-bit, Even parity, Stop 2-bit
Factory set value: Data 8-bit, Without parity, Stop 1-bit
SW3
Communication speed
3 4
OFF OFF
9600 bps
ON OFF
19200 bps
OFF ON
38400 bps
ON
ON
Don't set this one
Factory set value: 9600 bps
SW3
Protocol
5
OFF
RKC communication protocol
(Based on ANSI X3.28-1976 subcategory 2.5 B1)
See
6. RKC COMMUNICATION (P. 52)
.
ON
Modbus protocol
See
7. MODBUS (P. 105)
.
Factory set value: RKC communication protocol
SW3
Initialize
6
OFF Normal (It is initialized only in initialization execution)
ON
In power on, all module is initialized
Factory set value: Normal (It is initialized only in initialization execution)
Continued on the next page.