4. WIRING
IMS01J02-E4
39
RS-422A
Pin layout of modular connector (RS-422A)
H-PCP-J module
COM.PORT1
SG
6
T (A)
5
T (B)
4
SG
3
R (B)
2
R (A)
1
COM.PORT3
1
R (A)
2
R (B)
3
SG
4
T (B)
5
T (A)
6
SG
Connector pin number and signal details (RS-422A)
Pin No.
Signal name
Symbol
1
Receive data
R (A)
2
Receive data
R (B)
3 Signal
ground SG
4
Send data
T (B)
5
Send data
T (A)
6 Signal
ground SG
Diagram of RS-422A wiring
5
1
3
4
2
Shielded twisted pair wire
Pair wire
Touch panel
T (A)
T (B)
SG
R (A)
R (B)
SG
T (A)
T (B)
SG
R (A)
R (B)
H-PCP-J
6
(
)
(
)
(
)
(
)
(
)
(
)
(
)
(
)
Customer is requested to prepare a communication cable fit for the control unit to be
connected by the touch panel.
The 6-pin type modular connector should be used for the connection to the H-PCP-J module.
Recommended model: TM4P-66P (Manufactured by HIROSE ELECTRIC CO., LTD.)