7. MODBUS
IMS01J02-E4
140
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
H-DO-G manipulated
output value
[H-DO-G]
RO C
5.0 to
105.0 %
H-DO-G output limiter
high
[H-DO-G]
R/W
C
Output limiter low to 105.0 %
100.0
H-DO-G output limiter
low
[H-DO-G]
R/W C
5.0 % to Output limiter high
0.0
H-DO-G output cycle
time
[H-DO-G]
R/W
C
1 to 100 seconds
2
H-DO-G master channel
setting
[H-DO-G]
R/W
C
0 to The number of H-TIO-
module use
channel (0: Unused)
0
H-DO-G output ratio set
value
[H-DO-G]
R/W
C
0.001 to 9.999
1.000
H-DO-G Auto/Manual
transfer
[H-DO-G]
R/W
C
0: Auto 1: Manual
Setting will be invalid in ON/OFF control
and Heat/Cool control.
0
H-DO-G manual output
value
[H-DO-G]
R/W C
5.0 to
105.0 %
Setting will be invalid in ON/OFF control
and Heat/Cool control.
0.0
Continued on the next page.