7. MODBUS
IMS01J02-E4
138
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Cascade tracking
[H-CIO-A]
R/W M
0: Not provided
Cascade monitored value becomes zero.
1: Provided
Cascade monitored value just before is
hold.
0
Cascade data selection
[H-CIO-A]
R/W M
0: Manipulated outpur value
1: Temperature measured value (PV)
2: Temperature set value (SV)
3: Set value monitor
4: Temperature deviation
0
Cascade DI function
selection
[H-CIO-A]
R/W M
0: Unused
1: Cascade control ON/OFF only
2: Auto/Manual transfer only
3: DI1 valid
(Cascade control ON/OFF)
,
DI2 valid (Auto/Manual transfer)
3
DI process selection *
[H-SIO-A]
R/W M
0: Unused
1: H-SIO-A open/closed loop control
transfer only
2: Control RUN/STOP transfer only
3: H-SIO-A open/closed loop control
transfer and Control RUN/STOP transfer
3
* DI process selection setting or communication setting
: Valid
: Invalid
Transfer by external
contact input
Transfer via communication
DI process selection
H-SIO-A open/closed loop
control transfer
(See P. 130)
Control RUN/STOP transfer
(See P. 127)
0: Unused
1: H-SIO-A open/closed loop
control transfer only
2: Control RUN/STOP
transfer only
3: H-SIO-A open/closed loop
control transfer and
Control RUN/STOP
transfer
Continued on the next page.