8. FUNCTIONS
IMS01J02-E4
169
8.2.1 Display scale
This function scales the display range of the input value between
9999 to
10000. However, the
maximum span is 10000.
H-SIO-A input frequency at full scale:
Sets the frequency of encoder when display scale high value (full scale) is displayed.
Setting rage: 10 to 50000 Hz
Display scale high:
Sets the high limit value (full scale) of display scale.
Setting
rage:
9999 to
10000 (Span 10000 or less)
Display scale low:
Sets value to display when pulse input from encoder stopped.
Setting
rage:
9999 to
10000 (Span 10000 or less)
Decimal point position:
Sets the decimal point position of input display.
Setting rage: 0: No digit below decimal point
1: 1 digit below decimal point
2: 2 digits below decimal point
3: 3 digits below decimal point
Example: When set it in the following value
H-SIO-A input frequency at full scale: 100 Hz
Display scale high:
3000
Display scale low:
0
Decimal point position:
2 (2 digits below decimal point)
0 Hz
Display
30.00
100 Hz
Pulse input from
rotary encoder (frequency)
0.00