7. MODBUS
IMS01J02-E4
130
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
H-SIO-A control range
[H-SIO-A]
R/W
C
0.00 to 50.00 %
10.00
H-SIO-A input
frequency at full scale
[H-SIO-A]
R/W
C
10 to 50000 Hz
130
H-SIO-A output scale
high
[H-SIO-A]
R/W
C
H-SIO-A output scale low to 10000 *
400
H-SIO-A output scale
low
[H-SIO-A]
R/W C
9999 to H-SIO-A output scale high *
0
H-SIO-A correction
trigger
[H-SIO-A]
R/W C
0: Normal (Not executed)
1: Correction executed
2: Correction canceled
Processing time of correction execution or
cancel is about 1 second. Do not turn OFF
the power during the processing time. In
addition, maintain the setting more than 0.5
second in order to let it recognize
modification in setting modification.
0
H-SIO-A correction
actual measured value
[H-SIO-A]
R/W
C
Within display scale range *
0
H-SIO-A measuring
method
[H-SIO-A]
R/W
C
0: Periodic computation method
1: Pulse count method
0
H-SIO-A divide ratio
[H-SIO-A]
R/W
C
1 to 1000
Effective only for periodic computation
method.
10
H-SIO-A gate time
[H-SIO-A]
R/W
C
0.1 to 4.0 seconds
Effective only for pulse count method.
1.0
H-SIO-A auto zero time
[H-SIO-A]
R/W
C
1 to 100 seconds
5
H-SIO-A open/closed
loop control transfer
[H-SIO-A]
R/W
C
0: Closed loop control (PID control)
1: Open loop control
0
H-SIO-A alarm hold
cancel time
[H-SIO-A]
R/W
U
1 to 255 seconds
Setting will be invalid in no alarm hold
action.
60
* The position of the decimal point differs depending on Decimal point position (P. 131) setting.
Continued on the next page.