2. SPECIFICATIONS
IIMS01J02-E2
15
Digital output
Number of outputs:
8
points
Output type:
Open collector output
Number of common points:
Vcc: 2 points, GND: 2 points (8 points/common)
Isolation method:
Photocoupler
isolation
Load voltage:
12 to 24 V DC
Maximum load current:
0.1 A/point, 0.8 A/common
Output data
:
Digital output can be selected from the following:
−
Temperature alarm (Alarm 1, Alarm 2)
−
Heater break alarm (HBA)
−
Burnout
−
TI Alarm (Alarm 1, Alarm 2)
−
AI Alarm (Alarm 1, Alarm 2)
−
Control loop break alarm (LBA)
−
Temperature rise completion
−
Temperature rise completion
−
FAIL output
−
PLC communication status
−
Unused