4. WIRING
IMS01J02-E2
40
RS-485
Pin layout of modular connector (RS-485)
H-PCP-J module
COM.PORT1
SG
6
Unused
5
Unused
4
SG
3
T/R (B)
2
T/R (A)
1
COM.PORT3
1
T/R (A)
2
T/R (B)
3
SG
4
Unused
5
Unused
6
SG
Connector pin number and signal details (RS-485)
Pin No.
Signal name
Symbol
1
Send/receive data
T/R (A)
2
Send/receive data
T/R (B)
3 Signal
ground SG
4 Unused
-
5 Unused
-
6 Signal
ground SG
Diagram of RS-485 wiring
1
2
3
Shielded twisted pair wire
T/R (A)
T/R (B)
SG
T/R(A)
T/R(B)
SG
SG
Pair wire
Touch panel
H-PCP-J
6
Customer is requested to prepare a communication cable fit for the control unit to be
connected by the touch panel.
The 6-pin type modular connector should be used for the connection to the H-PCP-J module.
Recommended model: TM4P-66P (Manufactured by HIROSE ELECTRIC CO., LTD.)