6. RKC COMMUNICATION
IMS01J02-E2
100
Continued from the previous page.
Name
Iden-
tifier Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
PV bias unit selection
[H-TIO-H/J, H-CIO-A,
H-SIO-A]
JW
1
R/W
U
0: % (of span)
1: Unit of input range
0 *
H-PCP-J module
DO type selection
[H-PCP-J]
VU
6 R/W
C 0: No alarm function
1: Alarm 1/TI alarm 1
2: Alarm 2/TI alarm 2
3: Burnout
4: Heater break alarm (HBA)
5: Temperature rise
completion output
6: AI alarm 1
7: AI alarm 2
8: Control loop break alarm
(LBA)
9: FAIL output
10: PLC communication status
[Action]
1 to 4, 6 to 8:
Closed at alarm occurrence
5: Closed at temperature rise
completion
9: Open at fail occurrence
10: Closed at communication
with
PLC
Be action of energized case.
Action reverses in case of
de-energized.
(For the
energize/de-energized, see
H-PCP-J module DO
de-energized selection.)
CH1: 9
CH2: 1
CH3: 2
CH4: 3
CH5: 4
CH6: 5
CH7: 8
CH8: 10
* For the ZK-1103 specification, the factory set value is 1 (Unit of input range).