6. RKC COMMUNICATION
IMS01J02-E2
86
Continued from the previous page.
Name
Iden-
tifier
Digits Attri-
bute
Struc-
ture
Data range
Factory
set
value
Control RUN/STOP
holding *
[H-PCP-J]
X1
1 R/W
U 0: Not hold
Start-up from control stop
status
1: Hold
Start-up from before the
stop status
2: Start-up from control run
status
1
Temperature rise
completion hold
function
[H-PCP-J]
EK
1
R/W
U
0: Not hold
1: Hold
1
Interval time setting
COM.PORT1/
COM.PORT2
[H-PCP-J]
ZX
6
R/W
U
0 to 100 ms
1
Interval time setting
COM.PORT3
[H-PCP-J]
ZY
6
R/W
U
0 to 100 ms
1
* Action after power-ON differs depending on control RUN/STOP holding (Identifier X1) setting.
Status after power-ON
Control RUN/STOP
holding
(Identifier X1)
Operation mode transfer
(Identifier EI)
Control RUN/STOP transfer
(Identifier SR)
0: Not hold
Same as mode before the power
failure
“0: Control STOP”
Stopped until “1: Control RUN”
is instructed from the PLC or host
computer.
1: Hold
Same as mode before the power
failure
Same as status before the power
failure
Control before power failure is
maintained even if no PLC or
host computer is connected.
2: Start-up from control run
status
“1: Monitor” mode
However if the operation mode is
set to “0: Unused,” “0: Unused”
remains unchanged.
“1: Control RUN”
However, no control is performed
until the operation mode is set to
“3: Normal (perform control).”
For the Operation mode transfer (Identifier EI) and Control RUN/STOP transfer (Identifier
SR), see the
6.2 Communication Identifier List (P. 65)
.
Continued on the next page.