6. RKC COMMUNICATION
IMS01J02-E2
69
Continued from the previous page.
Name
Iden-
tifier Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
Alarm 1 set value
[H-TIO- , H-CIO-A,
H-SIO-A]
A1
6 R/W
C
Alarm 2 set value
[H-TIO- , H-CIO-A,
H-SIO-A]
A2
6 R/W
C
TC/RTD input:
Within input range or span
range
Current/voltage input,
H-SIO-A:
Within display scale range
or span range
See
Factory
set value
table of
Alarm 1/
Alarm 2
set value
*
Setting change rate
limiter
[H-TIO- , H-CIO-A,
H-SIO-A]
HH
6 R/W
C 0.0 to 100.0 % of
span/minute
0.0
Heater break alarm set
value 1
[H-TIO-A/C/D]
A3
6 R/W
C 0.0 to 100.0 A or
0.0 to 30.0 A
For the current transformer
(CT) input of the
H-TIO-A/C/D module.
0.0
Heater break alarm set
value 2
[H-CT-A]
A4
6 R/W
C 0.0 to 100.0 A or
0.0 to 30.0 A
For the current transformer
(CT) input of the H-CT-A
module.
0.0
*
Factory set value table of Alarm 1/Alarm 2 set value
Input type
Alarm type
Alarm 1 set value
Alarm 2 set value
TC/RTD input
Process high alarm
Input range (high limit)
Input range (high limit)
Process low alarm
Input range (low limit)
Input range (low limit)
Deviation high alarm, Deviation
high/low alarm, Band alarm
50
°
C 50
°
C
Deviation low alarm
−
50
°
C
−
50
°
C
No alarm function
Input range (high limit)
Input range (low limit)
Current/voltage input
Process high alarm
100.0 %
100.0 %
Process low alarm
0.0 %
0.0 %
Deviation high alarm, Deviation
high/low alarm, Band alarm
50 %
50 %
Deviation low alarm
−
50 %
−
50 %
No alarm function
100.0 %
0.0 %
Continued on the next page.