8. FUNCTIONS
IMS01J02-E2
176
8.2.5 Controls
This instrument controls with open loop control or PID control (closed loop control).
(1) Open loop control
In a deviation between the motor speed measured value and set value is larger than the H-SIO-A
control range set value, or the H-SIO-A open/closed loop control transfer is “1: Open loop control,”
the instrument is in open loop control, thereby outputting a constant control output value
corresponding to the motor speed set value.
H-SIO-A control range:
The motor speed measured value to perform PID control (closed loop control) and the deviation
from the motor speed set value are set.
Setting rage: 0.00 to 50.00 %
Example 1: When control output value is 10 V DC at maximum motor speed of 1000 mm/min.
Control output:
Voltage output 0 to 10 V DC
Output scale high: 1000
Display scale high: 1000
Output scale low: 0
Display scale low: 0
Example 2: When control output value is 9 V DC at maximum motor speed of 1000 mm/min
Control output:
Voltage output 0 to 10 V DC
Output scale high:
1111 *
Display scale high: 1000
Output scale low:
0
Display scale low: 0
Output limiter (high): 90.0 %
* Equivalent to display scale of 10 V DC
1000 (10 V DC)
500 (5 V DC)
When open loop control, 5 V DC
is outputted.
0 (0 V DC)
1000 mm/min
Motor speed set value
500 mm/min
0 mm/min
Output scale (Output voltage)
Display scale
1111 (10 V DC)
1000 (9 V DC)
500 (4.5 V DC)
When open loop control, 4.5 V
DC is outputted.
0 (0 V DC)
1111 mm/min
1000 mm/min
Motor speed set value
500 mm/min
0 mm/min
Output scale (Output voltage)
Display scale