6. RKC COMMUNICATION
IMS01J02-E2
78
Continued from the previous page.
Name
Iden-
tifier
Digits Attri-
bute
Struc-
ture
Data range
Factory
set
value
H-CT-A module heater
break alarm status
[H-CT-A]
AH
1 RO C
0: Normal
1: Break
2: Welding
Comprehensive alarm
status
[H-PCP-J]
AJ
6 RO U
0 to 2047 *
Alarm status is expressed as a
bit image in decimal number.
Positioning monitor
[H-TIO-K]
M8
6 RO C
−
5.0 to
+
105.0 %
Positioning output
neutral zone
[H-TIO-K]
V3
6
R/W
C
0.1 to 10.0 % of motor time
2.0
Motor time
[H-TIO-K]
TJ
6
R/W
C
5 to 1000 seconds
10
Integrated output limiter
[H-TIO-K]
OS
6
R/W
C
100.0 to 200.0 % of motor
time
150.0
Manual positioning
output value
[H-TIO-K]
OO
6 R/W
C
−
5.0 to
+
105.0 %
0.0
* Each alarm status is assigned as a bit image in binary numbers. However, send data from the SR Mini
HG SYSTEM be changed to decimal ASCII code from the bit image in binary numbers.
bit 15··························· bit 0
Bit image:
0000000000000000
Bit data 0: OFF 1: ON
Continued on the next page.
bit 0: Logical
OR
of alarm 1 status in all channels
bit 1: Logical
OR
of alarm 2 status in all channels
bit 2: Logical
OR
of burnout alarm status in all
channels
bit 3: Logical
OR
of heater break alarm status in all
channels
bit 4: Temperature rise completion status
bit 5: Logical
OR
of AI alarm 1 status in all channels
bit 6: Logical
OR
of AI alarm 2 status in all channels
bit 7: Logical
OR
of control loop break alarm status in
all channels
bit 8: Logical
OR
of TI alarm 1 status in all channels
bit 9: Logical
OR
of TI alarm 2 status in all channels
bit 10: Logical
OR
of TI burnout alarm status in all
channels
Bit 11 to bit 15 are unused.